Description
S260W S261W
GPRS/3G UMTS/GPS/SMS Temperature Logger:
The King Pigeon S260W S261W Temperature Logger inbuilt industrial
GSM and 3G WCDMA module, GPS optional, 4 Channel temperature
Inputs support Ultra-Low/Low/High/Ultra-High limit alarm
Monitoring.
One digital relay output with NC/NO contacts controlled by alarm
Event, SMS command or Rejected ller-ID(charge free).
With Internal memory, S260W S261W save historical data half a
Year for inquiry & download by PC software via USB cable or
KingCenter CMS-02 Remote Monitoring System via GPRS/UMTS TCP/IP,
And tracking the real time GPS location with optional GPS module.
Daily report, schedule upload, event upload via GPRS/UMTS to
Remote monitoring center (TCP/IP) or by SMS to users mobile phone
Available.
S260W S261W used for field monitoring in worldwide, we offer
GPRS/UMTS protocol for clients to build their own monitoring
Software/applications.
Features:
1) GSM and 3G WCDMA band,distribute worldwide applications
Available
2) ¨C55C degree to +125C degree (¨C67F degree to +257F
Degree) measurement range
3) SMS command or PC Software programming
4) User-programmable alarm thresholds (Ultra-
Low/Low/High/Ultra-High)
5) 6 numbers for receiving temperature alert and relay
Control
6) Relay control programmable when alarm thresholds exceed
7) Relay control by Caller-ID with free of charge, SMS,
GPRS,UMTS/HSDPA(*work with KingCenter CMS-02)
8) Record temperature data on internal memory:
A) Min interval: per 5mins, can save data on unit more than
6 months
B) Max interval: per 255mins,can save data on unit more than
10 years
9) Historical data download to PC (MS Excel format) via USB
10) Historical data query and download remotly by
GPRS,UMTS/HSDPA (*work with KingCenter CMS-02)
11) Supports 2 Server(Master and Slave) via GPRS,UMTS/HSDPA
12) Daily report, schedule upload, event upload program mable
13) AC/DC Power status monitoring, AC ON/OFF alert by SMS
14) Rechargeable Backup Battery inside(Approx.8hours standby)
15) IP67 Environmental protection enclosure(S261W)
16) GPS tracking module optional
Specifications:
1) Frequency: 2G:GSM900/1800MHz, 3G: 900/2100MHz UMTS
(default)
2G:GSM850/900/1800/1900MHz,3G:850/1900MHz UMTS (optional)
S260W S261W: the W is an identify letter of S260 S261, all of
These models with the same CE certificates.
1) Input Channel: 4*DS18B20 temperature input
2) Output: 1 Relay, NC/NO contacts, 7A/125V AC,
5A/250VAC,20A/14VDC
3) Temperature range: -55~+125C degree(¨C67F degree to +257F
Degree)
4) Accuracy: 0.5~1C degree from ¨C10C degree to +85C degree
5) Power Supply : 9~24VDC 2A
6) Power Consumption: 12V input Max.50mA/Average
7) SIM Card Supporting: 3V SIM Card
8) GSM Antenna: 50 ohm SMA Antenna interface
9) Backup Battery: 3.7V/1200mAH
10) Relative Humidity: 90%(condensation free)
11) Installation: 35mm DIN Rail (S260W)
IP67 Enclosure (S261W)
12) Connecting Wires: 2.5mm
13) Exterior Dimensions: 145*90*41mm (S260W)
180*140*60mm (S261W)
14) Net Weight: 250g
Packing List:
1) Main unit x1
2) 100~240VAC/12VDC 2A Power adaptor x1
3) DS18B20 temperature troide x2
4) Antenna x1
5) GPS Antenna x1 (*for GPS model optional) x1
6) User Manual & PC Software CD x1
Packing Size: 235 x 225 x 65mm
Gross Weight: 0.75KG
Optional:
GPS Module
DS18B20 Temperature probe with 1/5/10meters wire
DS18B20 Temperature probe with anticorrosion packing
PC Programming Software:
S26x Series PC Programming Tool (Windows XP and Windows 7/8 OS)
Functions:
A) Authorized users setting
B) GPRS/UMTS Parameters setting
C) Server IP and Port setting
D) Ultra-Low/Low/High/Ultra-High alarm thresholds
E) Query current values
F) Data recording interval
G) Historical data inquiry and export(MS Excel format)
H) SMS Daily report interval
I) GPRS/UMTS data upload interval
J) Relay action setting
K) Relay test
L) Date & Time adjustment
M) GPRS/UMTS data transceiving debug
Typical Project:
A. Temperature Alarm and Record
Storage temperature data on local unit,get alert SMS and phone
Call when temperature exceed pre-setting value, download the
Historical data by to PC Programming Software by USB every few
Months or half a year.
Suitble for: Server room,Warehouse,Cold room, Madicine center,
Drug store,Seafood stroge,Villa,Holiday house, Aquarium,
Supermarket, Hospital, Hotel, Billboard,Ads Signs LED,etc.
What you need:
S260W Standard Kit + SIM Card
PC Progrramming Software
Mobile Phone number for receiving alert
Computer with WinXP or Win7/8 OS
Steps:
1: Install S260W on site
2: Setting alert value and record interval time
3: Download historical data
B. Real Time Temperature Monitoring and Record
Storge temperature data on local unit,get alert SMS and phone
Call when temperature exceed pre-setting value, remote monitoring
Real time temperature and download historical data anytime
Anywhere by KingCenter CMS-02 via GPRS or UMTS/HSDPA TCP/IP.
Suitble for: Server room,Warehouse,Cold room, Madicine
Center,Drug store,Seafood stroge,Chain store,Shopping
Mall,Hospital,Water supplier,Fuel pipe,BTS station,etc.
What you need:
S260W Standard Kit + SIM Card
PC Progrramming Software
Mobile Phone number for receiving alert
KingCenter CMS-02 System
DNS or Server IP address and Port
Computer with WinXP or Win7/8 OS
Steps:
1: Install S260W on site
2: Setting alert value and record interval time & GPRS
3. Remote monitoring real time temperature value and Power
4: Download historical data
C. Real Time Temperature Monitoring and Record with GPS Tracking
Storge temperature data on local unit,get alert SMS and phone
Call when temperature exceed pre-setting value, get GPS tracking
Information on Google Map, Remote monitoring real time
Temperature and download historical data anytime anywhere by
KingCenter CMS-02 via GPRS/UMTS TCP/IP.
Suitble for: Refrigerated transport,Cold truck,Seafood
Transport,Logistics Management, Chain store,Food market,Hospital
Managerment,Water supplier,Fuel pipe,BTS station,etc.
What you need:
S260W+GPS Standard Kit + SIM Card
PC Progrramming Software
Mobile Phone number for receiving alert
KingCenter CMS-02 System
DNS or Server IP address and Port
Computer with WinXP or Win7/8 OS
Steps
1: Install S260W on site
2: Setting alert value and record interval time& GPRS/UMTS
Parameters
3. Remote monitoring real time temperature value,power and GPS
Location
4: Download historical data remotely
More details on : www.GSM-M2M.com
GPRS/3G/GPS/ Temperature Logger